Fire doors — six-monthly checks (Italy)
A list of checks and obligations with their cadence, ready to add to your agenda.
Italian kit for employers, building administrators and property managers with fire doors, fire shutters and fire exits. It covers the six-monthly periodic check under UNI 11473, the qualification of the technician who performs it, the maintenance tag and the service report, day-to-day visual surveillance between checks, the ban on wedging doors open by improvised means and the keeping of the product documentation. It deals with doors as compartmentation elements, not with door automation.
Questions about this product?
Ask what is in the manuals, how often the maintenance is due and what it takes to do it.
What it already has at hand
- No manual on this page
- 6 planned checks, the most frequent every month since the last inspection
Planned checks
Informative summary verified on 12/09/2026. It does not replace legal advice: the regulation cited prevails. If you spot an error, report it.
Some checks are only mandatory in certain countries: pick yours and the list follows.
- 01
Entrust the check to qualified personnel
Checking fire doors calls for a competent person from a specialised firm holding the qualification set out in UNI 11473: the door is certified as an assembly, and a seal replaced with a non-equivalent spare voids its declared performance. The person responsible for the property verifies the qualification when awarding or renewing the contract and keeps evidence of it together with the service reports.
continuous check, confirm every 12 monthsLegal obligationUNI 11473; D.M. 1 settembre 2021Italy onlySourceverified on 12/09/2026 - 02
Never wedge fire doors open by improvised means
A fire door held open with a wedge, a chain, a fire extinguisher propped against it or its closer unhooked compartments nothing: it is the commonest and cheapest way to cancel a fire-safety investment. Where the flow of people or goods needs the door open, the answer is an electromagnetic hold-open device linked to the detection system, not an improvisation. The person responsible writes this into the procedures and checks it during surveillance.
continuous check, confirm every 3 monthsCompany ruleItaly only - 03
Keep door closing under visual surveillance
Between one six-monthly check and the next a door fails in ways anyone can see: it does not close fully, the rebate is blocked by a mat or a carton, the panic bar jams, a seal comes away. Surveillance is a walk-round that the person in charge assigns to a designated worker and that needs no technician. The interval is not fixed by a standard: the person in charge sets it from risk and use, and a month is the starting value proposed here.
every month since the last inspectionCompany ruleItaly only - 04
Have the fire doors checked every six months
The periodic check must be carried out twice a year, by the end of the month it falls due, and verifies operation and full closing, the seal at the rebate, the condition of the intumescent strips, self-closing devices and coordinators, panic hardware and hinges. The duty lies with the employer or the person responsible for the property; the work is for a competent person from a specialised firm, not for the building's general handyman.
every 6 months since the last inspectionLegal obligationUNI 11473-1; UNI 11473-3; D.M. 1 settembre 2021Italy onlySourceverified on 12/09/2026 - 05
Update tag and report at every service visit
Traceability of the check rests on two documents: the maintenance tag fixed to the individual door, carrying the date and reference of the job, and the service report issued by the technician, describing the checks made, the faults found and the parts replaced. The technician fills them in, the person responsible for the property keeps them. The sources consulted describe these two documents and do not confirm a central register dedicated to this particular duty: anyone keeping a fire-safety register logs the visit there as well.
continuous check, confirm every 6 monthsRecommendedUNI 11473-3Italy only - 06
Keep the documentation of every installed door
The declaration of performance, the marking, the installation instructions and the maintenance manual are what let the technician know which spare parts are allowed and let an inspector know what performance the door claims. The person responsible collects them at handover and keeps them available for the whole life of the door, together with a list of the doors with position and fire-resistance class. It is an internal task, but without it the six-monthly check is blind.
continuous check, confirm every 12 monthsCompany ruleItaly only
In France this product has no planned checks: the ones listed apply to other countries.
In Germany this product has no planned checks: the ones listed apply to other countries.
In Switzerland this product has no planned checks: the ones listed apply to other countries.
In Austria this product has no planned checks: the ones listed apply to other countries.
In United Kingdom this product has no planned checks: the ones listed apply to other countries.
In Spain this product has no planned checks: the ones listed apply to other countries.
In Portugal this product has no planned checks: the ones listed apply to other countries.
In United States this product has no planned checks: the ones listed apply to other countries.
In Other country this product has no planned checks: the ones listed apply to other countries.