UNI 11473 isn't a label on the door, it's a service that repeats over time.
UNI 11473 is the Italian technical standard, in three parts, that defines how a fire-resistant door is installed and maintained: what the installer must do, what organisation the company must have, what competence the technician must demonstrate. Part 1 sets a periodic inspection at least every six months, and DM 1 settembre 2021 turns it into a reference tracked in the fire-safety inspection logbook. Here is what the standard requires and who needs to know it; for the operational checklist and the most common mistakes, the guide on maintaining fire doors develops the practical side.
What UNI 11473 covers, in brief
UNI 11473 — "Fire-resistant openable doors and windows and/or smoke control dispersion" — is the Italian technical standard that sets out the requirements for installing and periodically maintaining these elements. It applies to doors and windows whose performance was verified by an initial test under UNI EN 1634 (in its various parts), UNI 9723, or Circolare del Ministero dell'Interno 91/1961 — in practice, any door carrying a nameplate or documentation attesting its fire-resistance class.
The standard is split into three parts, published between 2013 and 2014. Part 1 sets the requirements for providing the installation and maintenance service — the one that concerns whoever manages the building most directly. Parts 2 and 3 concern whoever provides the service instead: the first defines the requirements of the organisation that does it (the installation or maintenance company), the second the knowledge, skills and competence required of the individual installer and maintenance technician.
As with fire extinguishers, UNI 11473 is a voluntary technical reference: it comes from the technical-standards world, not from a law. It becomes a concrete obligation because a higher-ranking rule refers to it — in this case DM 1 settembre 2021, which cites it among the applicable standards and requires the work to be logged in the fire-safety inspection register. Confusing the two things — technical standard and legal enforceability — is the most common mistake when talking about UNI 11473.
The standard's three parts, at a glance
Each part addresses a different audience: knowing which one applies to you saves you from reading the wrong section.
| Part | Year | What it defines |
|---|---|---|
| UNI 11473-1 | 2013 | The requirements for providing the installation and periodic maintenance service |
| UNI 11473-2 | 2014 | The requirements of the organisation — the company — providing the service |
| UNI 11473-3 | 2014 | The knowledge, skills and competence required of the installer and maintenance technician, under an EQF approach |
This guide focuses mainly on Part 1: it's the one that sets out what has to happen to the door, not which company has to make it happen.
Scope: which doors, which work
UNI 11473-1 covers two distinct moments in the life of a fire-resistant door: installation, meaning fitting it according to the manufacturer's instructions and the product's classification report, and periodic maintenance, meaning everything that keeps the conditions verified at initial testing in place over time. They're two different stages of the same kind: an incorrect installation can undermine the fire-resistance class just as much as a missed maintenance visit.
The standard doesn't certify the product — that's the job of the door's own marking and declaration of performance, defined elsewhere — but the service built around it: how it's installed, who checks it, with what competence. It's a distinction worth keeping in mind when reading a tender or a quote: "compliant with UNI 11473" describes who does the work and how, not the door itself.
The scope covers openable doors and windows, not fixed elements such as walls or floor slabs — those follow other standards. And it covers specifically fire resistance and/or smoke-control dispersion: two performances a door can have together or separately, depending on what the building's fire-safety design requires.
The stages set out in Part 1
Part 1 distinguishes three levels of activity, each with its own interval and responsible party — the same three-tier logic UNI 9994-1 uses for fire extinguishers.
- 01
Surveillance check
according to the internal plan (in practice, a frequent visual check)
staff on site
- 02
Periodic inspection
at least every 6 months
qualified maintenance technician (Part 3)
- 03
Routine and extraordinary maintenance
whenever the periodic inspection or a fault makes it necessary
qualified maintenance technician
The six-monthly inspection is the only fixed figure Part 1 puts in writing. For the point-by-point checklist of what's verified at that inspection, and the most common mistakes, the guide on maintaining fire doors covers the operational detail that this guide deliberately keeps brief.
Who needs to know UNI 11473, and why
It isn't a standard that only concerns whoever holds the screwdriver.
- Whoever manages the building: commissions the service and is accountable, if checked, for having chosen a company organised under Part 2
- The installer and the maintenance technician: Part 3 lists the knowledge and skills they must demonstrate, under a progressive EQF-based qualification
- Whoever keeps the fire-safety inspection register: DM 1 settembre 2021 requires the work required by UNI 11473 to be logged there
- Whoever drafts a tender specification: citing UNI 11473 without specifying the part leaves room for ambiguity about what's actually being required
- Whoever commissions the maintenance: checking that the chosen company is organised under Part 2 and its staff qualified under Part 3 is the minimum due diligence
A voluntary technical standard, not a stand-alone legal obligation
UNI 11473 isn't imposed by any law as such: it's a technical reference that DM 1 settembre 2021 refers to, effectively making it the criterion by which sound maintenance is judged. Describing it as "legally mandatory", full stop, is a simplification that loses the important part: the obligation comes from the decree that cites it, not from the UNI standard taken on its own. The distinction matters when weighing what happens if an inspection is missed.
What falls outside UNI 11473's scope
The standard doesn't cover design — that is, when a compartment requires a door of class EI, and which one, a matter for the fire-prevention code (DM 3 agosto 2015) — nor the manufacture and certification of the door as a product, governed at European level. It covers only the installation and maintenance service for a door that's already classified. If the question is "what class is needed here", the answer isn't in UNI 11473.
This guide is informational material: it does not replace the standards cited, the manufacturer's manual or the judgement of a qualified technician. ToriSet organises deadlines and documents; it does not certify compliance.
The same deadlines, without the spreadsheet to recalculate.
Anyone who reaches the end of a guide like this one usually keeps the dates on a spreadsheet, on a tag, or from memory. It works as long as the assets are few and there is one person keeping track. Here is what changes with a logbook.
A spreadsheet with one date per row, on a single computer
A shared logbook: whoever opens the record sees what's due and who did the last job
You recalculate the next deadline yourself, if you remember
ToriSet calculates it from the last job: by months, by hours of use, or whichever comes first
The reminder is a sticky note or a diary
An email 30, 14, 7 and 1 day before, to you and to whoever has to act
Reports and invoices in a folder, to go looking for when needed
Attached to the job, on the product's record
What changes from one country to the next.
UNI 11473 is an Italian technical standard, in three parts: it doesn't apply outside national borders. None of the other four countries has a single standard covering installation, organisation and technician competence the same way: the task is spread across a regulation, a standard on the hold-open device, and the manufacturer's manual. Below is what plays UNI 11473's role in each, with the caveat that the source that counts remains the one cited, together with the door's manual.
Your choice is remembered in this browser.
Italy
References
UNI 11473-1:2013
The requirements for providing the installation and periodic maintenance service for fire-resistant openable doors and windows and/or for smoke-control dispersion.
UNI 11473-3:2014
The knowledge, skills and competence required of the installer and maintenance technician.
DM 1 settembre 2021
Refers to UNI 11473 among the applicable standards and requires the work to be logged in the fire-safety inspection register.
Intervals
Surveillance check
according to the internal plan (in practice, a frequent visual check)
staff on site
Periodic inspection
at least every 6 months
qualified maintenance technician (Part 3)
Routine and extraordinary maintenance
whenever the periodic inspection or a fault makes it necessary
qualified maintenance technician
NoteThe only one of the five with a technical standard dedicated to the whole service — installation, organisation and competence — rather than just the hold-open device.
France
References
Code du travail
Places firefighting equipment, doors included, and keeping it serviceable, in the employer's hands for workplaces.
Arrêté du 25 juin 1980
The safety regulation for ERPs (buildings open to the public): article CO 48 requires fire doors to stay functional and be kept serviceable.
NF S61-933
The standard on the operation and maintenance rules for fire-safety systems (SSI): it also covers actuated safety devices (DAS), self-closing fire doors included, checked by a competent technician.
Intervals
Periodic check (automatic and semi-automatic doors in workplaces)
at least every 6 months (arrêté du 21 décembre 1993, art. 9)
competent technician
Maintenance (ERP)
annual in practice, logged in the safety register
competent technician
NoteThere's no single French standard covering installation and maintenance the way UNI 11473 does: the task is split between building regulation and the standard on maintaining safety systems.
Germany
References
DIN 14677
Covers any electromechanical hold-open device (Feststellanlage) that keeps the door open until the alarm: annual maintenance and a functional test at least quarterly.
Musterbauordnung (MBO)
The model building code, adopted with variations by each Land: requires compartmentation elements, doors included, to be kept serviceable, without setting a single national numeric interval.
Intervals
Maintenance of the hold-open device (Feststellanlage)
at least once a year
qualified technician
Maintenance of the door itself
as set by the manufacturer's manual, annual in practice
specialised technician
NoteIn Germany there's no direct equivalent of UNI 11473 for the door itself: only the hold-open device, if fitted, has a technical standard with precise figures, DIN 14677 for the door closer/Feststellanlage.
Switzerland
References
Brandschutzvorschriften VKF / AICAA
Place on the owner the duty to keep compartmentation elements, doors included, serviceable, without setting a single interval for the whole country.
Intervals
Maintenance and functional check
annual in practice; the applicable interval is set by the fire regulations and the cantonal authority
qualified personnel
NoteAs with fire extinguishers, enforcement in Switzerland is cantonal: check what your canton's fire authority requires and what the door's manual says.
Austria
References
ÖNORM B 3850
Requirements and marking for hinged and pivoted fire doors; refers maintenance to the manufacturer's instructions.
ÖNORM B 3852
The same for sliding, roller and folding fire doors.
TRVB B 148
The technical directive on hold-open devices (Feststellanlagen): requires a monthly functional check.
Intervals
Professional maintenance
once a year, under the cited ÖNORM standards and the manufacturer's manual
qualified person
Functional check of the hold-open device
monthly
instructed person
NoteÖNORM B 3850/B 3852 are the closest in scope to UNI 11473, because they cover the door as a product and shape its maintenance: they remain product standards, though, not a three-part service like the Italian one.
What we get asked most.
What is UNI 11473?
It's the Italian technical standard, in three parts, that sets the requirements for installing and periodically maintaining fire-resistant openable doors and windows and/or for smoke-control dispersion. Part 1 (2013) covers the installation and maintenance service, Part 2 (2014) the organisation providing it, Part 3 (2014) the competence of whoever carries it out.
How often is the inspection under UNI 11473-1 required?
Part 1 sets a periodic inspection at least every six months, carried out by a qualified maintenance technician, alongside a more frequent visual surveillance check left to whoever works on site. It's the only figure the standard puts in writing: the actual maintenance follows what the inspection finds, or what the manufacturer's manual requires.
Is UNI 11473 mandatory?
Not on its own: it's a voluntary technical standard. It becomes a concrete reference because DM 1 settembre 2021 refers to it among the applicable standards and requires the work to be logged in the fire-safety inspection register. The distinction between a technical standard and the law that refers to it is the same one that applies to UNI 9994-1 for fire extinguishers.
Who can install and maintain doors under UNI 11473?
Part 3 defines the knowledge, skills and competence required of whoever installs and maintains: knowing how to fit a door isn't enough, a specific qualification has to be demonstrated. Part 2 also requires the company they work for to be organised under its own requirements, not just the individual technician.
What's the difference between UNI 11473 and UNI 11473-1?
"UNI 11473" without a part number refers to the standard as a whole, in three parts. "UNI 11473-1" is the part specifically covering the installation and maintenance service, the one whoever manages the building deals with; Parts 2 and 3 cover the organisation and the competence of whoever provides the service.
Does ToriSet help you keep to UNI 11473?
ToriSet helps you keep to the deadlines set by the applicable standard: you record each door with its model and location, the next inspection date is calculated using the correct interval, and reminders arrive in time. The installation and maintenance service itself remains the responsibility of a company and a technician qualified under Parts 2 and 3 of the standard.