EnvironmentCompliance kit

Emissions and industrial environment (Spain)

A list of checks and obligations with their cadence, ready to add to your agenda.

For Spanish businesses with potentially air-polluting activities (APCA), refrigeration or air-conditioning plant using fluorinated gases, water discharges or noisy operations. Covers the APCA permit or notification, periodic emission checks by an accredited control body, the emissions register, the PRTR declaration, F-gas leak checks, the discharge authorisation and acoustic control. Does not cover the integrated environmental permit as a whole, environmental impact assessment or sector-specific emission limits.

AI assistant

Questions about this product?

Ask what is in the manuals, how often the maintenance is due and what it takes to do it.

What it already has at hand

  • No manual on this page
  • 11 planned checks, the most frequent every year by 31 March

Planned checks

Informative summary verified on 11/09/2026. It does not replace legal advice: the regulation cited prevails. If you spot an error, report it.

Version 1Countries coveredEuropean Union
Checks by country

Some checks are only mandatory in certain countries: pick yours and the list follows.

  1. 01

    Keep the F-gas equipment records

    For each piece of equipment subject to leak checks the operator keeps a record of the quantity and type of gas charged, the quantities recovered, the check results and the details of the company or technician involved. The record must be kept for at least 5 years and made available to the competent authority on request. Proof: the equipment record, on paper or electronic. Applies to operators of equipment subject to leak checks under art. 5 of Regulation (EU) 2024/573.

    continuous check, confirm every 12 monthsLegal obligationRegulation (EU) 2024/573 art. 7European Union onlySourceverified on 11/09/2026
  2. 02

    Carry out the F-gas leak check

    The operator of equipment containing fluorinated gases has leak checks performed by certified personnel, at intervals set by the charge expressed in tonnes of CO2 equivalent. Any leak found must be repaired and the check repeated after at least 24 hours of operation and within 1 month. Proof: the check report signed by the certified technician. Applies to equipment with at least 5 t CO2eq of Annex I gases, or at least 1 kg of Annex II gases, every 12 months from 5 to under 50 t CO2eq, every 6 months from 50 to under 500 t and every 3 months from 500 t upwards, with the intervals doubled where a leak detection system is installed; hermetically sealed equipment below 10 t CO2eq and certain electrical switchgear are excluded.

    every 12 months since the last inspectionLegal obligationRegulation (EU) 2024/573 art. 5; RD 115/2017European Union onlySourceverified on 11/09/2026